(3) Electrical Dimensions

Feeding system … 750 V DC parallel feed

Feeding voltage … Standard 750 V DC

Maximum 900 V DC

Minimum 500 V DC

Maximum current collected … 860 A per two cars

Basic unit of power consumption … 40 Wh/ton-km

Cnntact rail resistance … 21.5 mΩ/km

Running rail resistance … 21.5 mΩ/km (two rails in parallel)

 

7.4.3 Substation

 

(1) Sfandard Distance between Substations

The standard distance between substations is determined by the length of feed distance to secure the minimum feeding voltage of 500 V. Table 7.4-1 shows the estimated maximum feed distances for one-way and parallel feeding from adjacent substations.

 

122-1.gif

For standard distance between substations, we adopted about 2 km for one-way feed and about 6 km for parallel feed, including an allowance based on the data for four-car trains in Table 7.4-1.

 

(2) Substation Incations

We determined substation locations by taking into account the following.

(a) Although substations can be centered between adjacent stations, we plan to consfuct them near stations to share lands and bui1dings with stations and reduce mnstruction costs.

(b) As four-car trains are planned for the future, the unit rectifier capacity shall be about 2,500 kW.

(c) Substation locations shall finally be determined by surveying sites after other conditions have been finalized.

 

 

 