406 Curb Ramps
406.1 General. Curb ramps on accessible routes
shall comply with 406 and with 405.2, 405.4, 405.5 and 405.10.
406.2 Counter Slope. Counter slopes of adjoining
gutters and road surfaces immediately adjacent to the curb ramp shall not be steeper
than 1:20. The adjacent surfaces at transitions at curb ramps to walks, gutters
and streets shall be at the same level.
406.3 Sides of Curb Ramps. Curb ramps located
where pedestrians must walk across the ramp shall have flared sides. Slope of
the flares shall not be steeper than 1:10. Where the width of the walking surface
at the top of the ramp and parallel to the run of the ramp is less than 48 inches
(1220 mm) wide, the flared sides shall have a slope not steeper than 1:12, Curb
ramps with returned curbs shall be permitted where pedestrians would not normally
walk across the ramp.
406.4 Handrails. Handrails are not required on
curb ramps.
406.5 Location at Marked Crossings. Curb ramps
at marked crossings shall be wholly contained within the markings, excluding any
flared sides.
406.6 Diagonal Curb Ramps. Diagonal or corner
type curb ramps with returned curbs or other well-defined edges shall have the
edges parallel to the direction of pedestrian flow. The bottom of diagonal curb
ramps shall have 48 inches (1220 mm) minimum of clear space. Diagonal curb ramps
provided at marked crossings shall provide the 48 inches (1220 mm) minimum clear
space within the markings. Diagonal curb ramps with flared sides shall have a
segment of straight curb 24 inches (610 mm) long minimum located on each side
of the curb ramp and within the marked crossing.
406.7 Islands. Raised islands in crossings shall
be cut through level with the street or have curb ramps at both sides and shall
have a level area at least 48 inches (1220 mm) long minimum by 36 inches (915
mm) wide minimum in the part of the island intersected by the crossings.
407 Elevators
407.1 General. New elevators required to be accessible
shall comply with 407.2. New destination-oriented elevators required to be accessible
shall comply with 407.3. New limited use/limited application elevators required
to be accessible shall comply with 407.4. Altered elements of existing elevators
shall comply with 407.5.
407.2 New Elevators. New accessible elevators
shall comply with 407.2.1 through 407.2.13 and with ASME/ANSI Al7.1. They shall
be passenger elevators as classified by ASME/ANSI A17.1.
407.2.1 Automatic Operation. Elevator operation
shall be automatic. Each car shall be equipped with a self-leveling feature that
will automatically bring and maintain the car at floor landings within a tolerance
of 1/2 inch (13 mm) under rated loading to zero loading conditions.
407.2.2 Call Buttons. Call buttons in elevator
lobbies and halls shall be located vertically between 35 inches (890 mm) and 48
inches (1220 mm) above the floor, measured to the centerline of the button. A
clear floor space complying with 305 shall be provided. Such call buttons
shall have visible signals to indicate when each call is registered and when each
call is answered. Call buttons shall be 3/4 inch (19 mm) minimum in the smallest
dimension. The button that designates the up direction shall be located above
the button that designates the down direction. Buttons shall be raised or flush.
Objects located beneath hall call buttons shall protrude 4 inches (100 mm) maximum
into the clear floor space.
407.2.3 Hall Signals. A visible and audible signal
shall be provided at each hoistway entrance to indicate which car is answering
a call and the direction of travel. Alternatively, in-car signals shall be located
in cars, visible from the floor area adjacent to the hail call buttons, and shall
comply the requirements of this section.
407.2.3.1 Audible Signals. Audible signals shall
sound once for the up direction and twice for the down direction, or shall have
verbal annunciators that state the word "up" or "down." Audible signals or verbal
annunciators shall have a frequency of 1500 Hz maximum. The audible signal or
verbal annunciator shall be 20 dBA minimum and 80 dBA maximum, measured at the
annunciator.
407.2.3.2 Visible Signals. Visible signals shall
comply with 407.2.3.2.1 through 407.2.3.2.3.
407.2.3.2.1 Height. Hall signal fixtures shall
be centered at 72 inches (1830 mm) minimum above the floor or ground.
407.2.3.2.2 Size. The visible signal elements
shall be 2-1/2 inches (64 mm) minimum in the smallest dimension.
407.2.3.2.3 Visibility. Signals shall be visible
from the floor area adjacent to the hall call button.
407.2.4 Tactile Signs on Hoistway Entrances.
Tactile character and Braille floor designations shall be provided on both jambs
of elevator hoistway entrances and shall be 60 inches (1525 mm) above the floor,
measured from the baseline of the characters. A tactile star shall also be provided
on both jambs at the main entry level. Such characters shall be 2 inches (51 mm)
high and shall comply with 703.2.
407.2.5 Doors. Elevator doors shall be the horizontal
type. Elevator hoistway and car doors shall open and close automatically. Elevator
doors shall be provided with a reopening device that shall stop and reopen a car
door and hoistway door automatically if the door becomes obstructed by an object
or person. The device shall be activated by sensing an obstruction passing through
the opening at 5 inches (125 mm) and 29 inches (735 mm) above the floor. The device
shall not require physical contact to be activated, although contact may occur
before the door reverses. Door reopening devices shall remain effective for 20
seconds minimum.
407.2.6 Door and Signal Timing for Hall Calls.
The minimum acceptable time from notification that a car is answering a call or
designation of which car is assigned to a lobby destination floor entry until
the doors of that car start to close shall be calculated from the following equation:
T = D/(1.5 ft/s) or T = D/(455 mm/s) = 5 seconds minimum
where T equals the total time in seconds and D equals the distance (in feet or millimeters) from the point in the lobby or corridor 60 inches (1525 mm) directly in front of the farthest call button controlling that car to the centerline of its hoistway door. For cars with in-car lanterns, T begins when the signal is visible from the point 60 inches (1525 mm) directly in front of the farthest hall call button and the audible signal is sounded.
407.2.7 Door Delay for Car Calls. Elevator doors
shall remain fully open in response to a car call for 3 seconds minimum.
407.2.8 Inside Dimensions of Elevator Cars. Clear
width of elevator doors and inside dimensions of elevator cars shall comply with
Table 407.2.8.
Table 407.2.8 Elevator Door and Car Sizes
|
MINIMUM DIMENSIONS |
Door Location |
Door Clear Width |
inside Car, Side to Side |
inside Car, Back Wall to Front Return |
Inside Car, Back Wall to inside Face of Door |
Centered |
42 inches(1065 mm) |
80 inches(2030 mm) |
51 inches (1295 mm) |
54 inches (1370 mm) |
Side (Off-centered) |
36 inches (915 mm)1 |
68 inches (1725 mm) |
51 inches (1295 mm) |
54 inches (1370 mm) |
Any |
36 inches (915 mm)1 |
54 inches (1370 mm) |
80 inches (2030 mm) |
80 inches (2030 mm) |
Any |
36 inches (915 mm)1 |
60 inches (1525 mm)2 |
60 inches (1525 mm)2 |
60 inches (1525 mm)2 |
|
407.2.9 Floor Surfaces. Floor surfaces in elevator
cars shall comply with 302. The clearance between the car platform sill
and the edge of any hoistway landing shall be 1-1/4 inch (32 mm) maximum.
407.2.10 Illumination Levels. The level of illumination
at the car controls, platform, car threshold and car landing sill shall be 5 footcandles
(54 lux) minimum.
407.2.11 Car Controls. Elevator controls shall
comply with 407.2.11.1 through 407.2.11.4.
407.2.11.1 Buttons. Buttons shall be 3/4 inch
(19 mm) minimum in their smallest dimension. Buttons shall be raised or flush.
Buttons shall be arranged with numbers in ascending order. When two or more columns
of buttons are provided they shall read from left to right. Keypads, where provided,
shall be in a standard telephone keypad arrangement.
407.2.11.2 Designations and indicators for Control
Buttons. Control buttons shall be identified by tactile characters complying
with 703.2. Characters and Braille shall be placed immediately to the left
of the button to which the designations apply. The control button for the main
entry floor and control buttons, other than remaining buttons with floor designations,
shall be identified with tactile symbols as shown in Table 407.2.11.2. Buttons
with floor designations shall be provided with visible indicators to show that
a call has been registered. The visible indication shall extinguish when the car
arrives at the designated floor. Where provided, telephone-style keypad buttons
shall be identified by tactile characters complying with 703.2 except that Braille
is not required. Characters shall be centered on the corresponding keypad button.
Table 407.2.11.2 Elevator Control Button Identification |
Control Button |
Tactile Symbol |
Braille Message |
Emergency Stop |
[insert symbol] |
[insert symbol]"ST"OP Three cells |
Alarm |
[insert symbol] |
[insert symbol] AL"AR"M Four cells |
Door Open |
[insert symbol] |
[insert symbol]OP"EN" Three cells |
Door Close |
[insert symbol] |
[insert symbol]CLOSE Five cells |
Main Entry Floor |
[insert symbol] |
[insert symbol]MA"IN" Three cells |
Phone |
[insert symbol] |
[insert symbol]PH"ONE"Four cells |
|
407.2.11.3 Height. Buttons with floor designations
shall be located 48 inches (1220 mm) maximum above the floor. Emergency controls,
including the emergency alarm, shall be grouped at the bottom of the panel. Emergency
control buttons shall have their centerlines 35 inches (890 mm) minimum above
the floor.
EXCEPTION: Where the elevator serves more than 16 openings and parallel approach is provided, buttons with floor designations shall be located 54 inches (1370 mm) maximum above the floor.
407.2.11.4 Location. Controls shall be located
to accommodate a forward reach or side reach as specified in 308.
407.2.12 Car Position Indicators. In elevator
cars, audible and visible car location indicators shall be provided.
407.2.12.1 Visible Indicators. Indicator shall
be located above the car control panel or above the door. Numerals shall be 1/2
inch (13 mm) high minimum. As the car passes a floor and when a car stops at a
floor served by the elevator, the corresponding character shall illuminate.
407.2.12.2 Audible indicators. The audible signal
shall be 20 dBA minimum and 80 dBA maximum, measured at the annunciator, and shall
have a frequency of 1500 Hz maximum. The signal shall be an automatic verbal announcement
which announces the floor at which the car has stopped except an audible signal
which sounds as the car passes or stops at a floor served by the elevator shall
be acceptable for elevators with a rated speed of 200 feet per minute (1.02 m/s)
or less.
407.2.13 Emergency Communications. Emergency
two-way communication systems between the elevator car and a point outside the
hoistway shall comply with ASME/ANSI A17.1. The highest operable part of a two-way
communication system shall be 48 inches (1220 mm) maximum above the floor. The
device shall be identified by tactile characters complying with 703.2 located
adjacent to the device. If the system uses a handset, the cord from the panel
to the handset shall be at least 29 inches (735 mm) minimum. The car emergency
signaling device shall not be limited to voice communication. If instructions
for use are provided, essential information shall be presented in both tactile
and visual form.
407.3 New Destination-Oriented Elevators. New
accessible destination-oriented elevators shall comply with 407.2.1, 407.2.4 through
407.2.10, and 407.2.13. Such elevators shall also comply with 407.3.1 through
407.3.5 and ASME/ANSI A17.1. They shall be passenger elevators as classified by
ASME/ANSI A17.1.
407.3.1 Call Buttons. Call buttons shall be located
vertically between 35 inches (890 mm) and 48 inches (1220 mm) above the floor,
measured to the centerline of the button. A clear floor space complying with 305
shall be provided. Call buttons shall be 3/4 inch (19 mm) minimum in the smallest
dimension. Buttons shall be raised or flush. Objects located beneath hall call
buttons shall protrude 4 inches (100 mm) maximum into the clear floor space. A
keypad or other means for the entry of destination information shall be provided.
Keypads, where provided, shall be in a standard telephone keypad arrangement.
Visible and audible signals which indicate which elevator car to enter shall be
provided.
407.3.2 Hall Signals. A visible and audible signal
shall be provided to indicate a car destination corresponding with 407.3.1. The
audible tone and verbal announcement shall be the same as those given at the call
button or call button keypad. Each elevator in a bank shall have audible and visible
means for differentiation.
407.3.2.1 Visible Signals. Visible signals shall comply with 407.3.2.1.1 through 407.3.2.1.3.
407.3.2.1.1 Height. Hall signal fixtures shall
be centered at 72 inches (1830 mm) minimum above the floor or ground.
407.3.2.1.2 Size. The visible signal elements
shall be 2-1/2 inches (64 mm) minimum in the smallest dimension.
407.3.2.1.3 Visibility. Signals shall be visible
from the floor area adjacent to the hoistway entrance.
407.3.3 Car Controls. Emergency controls, including
the emergency alarm, shall have their centerlines 35 inches (890 mm) minimum and
48 inches (1220 mm) maximum above the floor. Buttons shall be 3/4 inch (19 mm)
minimum in their smallest dimension. Buttons shall be raised or flush. Controls
shall be located to accommodate a forward reach or side reach as specified in
308.
407.3.4 Car Position indicators. in elevator
cars, audible and visible car location indicators shall be provided.
407.3.4.1 Visible Indicators. Indicators shall
be located above the car control panel or above the door. Numerals shall be 1/2
inch (13 mm) high minimum. A display shall be provided in the car with visible
indicators to show car destinations. The visible indicators shall extinguish when
the call has been answered.
407.3.4.2 Audible indicators. An automatic verbal
announcement which announces the floor at which the car has stopped shall be provided.
The announcement shall be 20 dBA minimum and 80 dBA maximum, measured at the annunciator.
407.3.5 Elevator Car Identification. In addition
to the tactile signs required by 407.2.4. a tactile elevator car identification
shall be placed immediately below the hoistway entrance floor designation. The
characters shall be 2 inches (51 mm) high and shall comply with 703.2.
Notes: |
1. |
A tolerance of minus 5/8 inch (16 mm) is permitted. |
|
2. |
Other car configurations that provide a wheelchair turning space complying with 304 with the door closed are permitted. |
|