13.3.4. A vent system or other means shall be provided to permit the discharge from the vessel of hydrogen gas released by battery.
UK 66
The proposal is be changed into:
13.9.3. The ends of every conductor shall be securely terminated by means which contain all the strands of the conductor.
13.9.3.1 Solder shall not be the sole means of mechanical connection
13.9.3.2. Cable sockets and clamps shall be of such dimensions and design that the maximum current likely to flow through them will not cause the rated operating temperature of the cable insulation to be exceeded.
13.9.3.3 The means of fixing of conductors and terminals should be capable of withstanding the thermal and dynamic effects of short-circuits
13.9.3.4 Soldering fluxes containing acid or other corrosive substances should not be used.
13.9.3.5. The ends of mineral-insulated metal sheathed cables shall be so sealed as to prevent the ingress of moisture. Such sealing materials and any material used to insulate the conductors where they emerge from the insulation shall have adequate
UK 67
The proposal based on the UK national standard has been rejected.
The proposal is not in line with IEC 60364 part 6 and may form the basis for a further amendment of this standard if the UK decides to bring this up as a new work proposal.
The WG decided to remain with the existing text.
PL 29
A Note will be added at 14.2
・ "Note - care should be taken on electronic equipment to ensure that no damage is sustained due to the application of test voltages."
PL 30
Agreed
PL 31
Agreed