3.4.2.3.2 Inert gas agents

Q= V[294/(273+T)]・(P/1.013)・ln[100/(100-C)]

where:

Q= volume of inert gas, measured at 294 K and 1.013 bar, discharged, m3

V= volume of test enclosure, m3

T= test enclosure temperature, Celsius.

P= test enclosure pressure, bar

C= gaseous agent concentration, volume per cent.

 

3.5 Procedure

3.5.1 Fuel levels in trays

The trays used in the test should be filled with at least 30mm fuel on a water base. Freeboard should be 150±10mm.

 

3.5.2 Fuel flow and pressure measurements

For spray fires, the fuel flow and pressure should be measured before and during each test.

 

3.5.3 Ventilation

3.5.3.1 Pre-burn period

During the pre-burn period the test enclosure should be well ventilated. The oxygen concentration, as measured at mid-room height, shall not be less than 20 volume per cent at the time of system discharge.

3.5.3.2 End of pre-burn period

Doors, ceiling hatches, and other ventilation openings should be closed at the end of the pre-burn period.

 

3.5.4 Duration of test

3.5.4.1 Pre-burn time

Fires should be ignited such that the following burning times occur before the start of agent discharge:

.1 sprays-5 to 15s

.2 trays-2 min

.3 crib-6 min

 

 

 