TEST METHOD FOR FIRE TESTING OF FIXED GAS FIRE-EXTINGUISHING SYSTEMS

 

1 Scope

1.1 This test method is intended for evaluating the extinguishing effectiveness of fixed gas fire-extinguishing systems for the protection of machinery spaces of category A and cargo pump-rooms.

 

1.2 Fire-extinguishing systems presently covered in SOLAS regulation II-2/5, as amended, are excluded.

 

1.3 The test method covers the minimum requirements for fire-extinguishing.

 

1.4 This test method is applicable to gases, liquefied gases and mixtures of gases. The test method is not valid for extinguishant gases mixed with compounds in solid or liquid state at ambient conditions.

 

1.5 The test programme has two objectives: (1) establishing the extinguishing effectiveness of a given agent at its tested concentration, and (2) establishing that the particular agent distribution system puts the agent into the enclosure in such a way as to fully flood the volume to achieve an extinguishing concentration at all points.

 

2 Sampling

The components to be tested should be supplied by the manufacturer together with design and installation criteria, operational instructions, drawings and technical data sufficient for the identification of the components.

 

3 Method of test

3.1 Principle

This test procedure enables the determination of the effectiveness of different gaseous agent extinguishing systems against spray fires, pool fires and class A fires.

 

3.2 Apparatus

3.2.1 Test room

The tests should be performed in 100m2 room, with no horizontal dimension less than 8 m, with a ceiling height of 5 m. The test room should be provided with a closable access door measuring approximately 4 m2 in area. In addition, closable ventilation hatches measuring at least 6 m2 in total area should be located in the ceiling.

 

 

 